Properties :
• ClO2 production, measurement and monitoring with a single system
• Easy and fast operation thanks to the 7 '' Touchscreen
• Volumetric chlorine dioxide production depending on the meter by measuring the flow rate of the water passing through the line
• Flexible operation with 4 different operating modes
- Constant dosage with rate adjustment
- Volumetric dosage
- Measurement and Controlled dosage (Optional)
- Volumetric dosing and measurement controlled (Optional)
• Ensuring maximum operational safety and purity of CIO2 produced using stroke sensor monitoring pumps
• Excellent quality management thanks to the recording of all operating parameters
• Monitoring of operating parameters and maintenance intervals
• Flow sensor indicating dilution line and flow at system inlet
• 4-20mA controlled digital dosing pumps with automatic bleed valve
• Convenience in business plan thanks to graphs showing chemical consumption and chlorine dioxide production
Models :
Stock Code | Model | Description |
109111100000000 | CHLORDIOXIT GENERATOR 100 | 100Gr/H Chlordioxit Generator |
109111100001000 | CHLORDIOXIT GENERATOR 200 | 200Gr/H Chlordioxit Generator |
Why Chlorine Dioxide?
Chlorine dioxide performs a strong and effective disinfection process regardless of the value in a very wide pH range. Like disinfectants in
chlorine and other halogen groups, bound chlorine does not form chloramine and Trihalomethane (THM).
It is superior to other disinfectants with its free radical state, selective, long, and effective disinfection feature and not creating harmful
substances after the procedure.
It is effective in all known bacteria and viruses. Virus contamination (meeting), where other disinfectants are insufficient, is extremely
effective in dangerous pathogens such as Giardia, Legionella, Cryp-toxoridium. It dissolves the bioflim layers and does not allow them to form again.
After disinfection, its protective effect in water continues for a long time. It regulates the alkalinity and hardness of water and removes heavy metals
(such as Fe-Mn), Phenol and Amine groups from water.
The most effective way of using Chlorine Dioxide is to convey the gas form and the liquid form that has not lost its effect to the process
water in its freshest form in the closed system with on-site production. For this, the use of chlorine dioxide generators is becoming increasingly
widespread.
Areas of Usage :
• Municipal drinking water and wastewater treatment
• Industrial process, service water and coolant
• Irrigation water disinfection in agriculture
• Food factories
• Poultry and livestock farms
• Fruit and vegetable washing juices
Technicial Specifications :
Chlorine Dioxide Dosing Capacity* max./hour |
Max Operating Pressure |
Operating Temperature | Dimensions | Bypass Connection Dimensions |
g/h | bar | °C | BxExY (cm) | (mm) |
100 | 10 | 0 - 45 | 120x90x40 | DN25 |
200 | 10 | 0 - 45 | 230x90x40 | DN25 |
Dosing Pump Type | Pump Dosing Capacity* |
Power Consumption |
Hose Connection Dimensions |
Max. Pump Suction (height) |
bar | W | (mm) | (m) | |
LARA DMS | 1,3 | 28 | 4 X 6 | 1,5 |
LARA DMS | 2,9 | 45 | 4 X 6 | 1,5 |
Inputs |
Configurable 1 analog input 0/4-20mA |
6 digital inputs (Flow, Chemical Level, Dosage Warning, etc. ) | |
Sample water flow monitoring, external fault | |
1 digital input for water meter 0.25-20 Hz | |
1 digital input for water meter 10-10.000 Hz | |
Outputs |
1 configurable analog output 0/4-20mA |
2 analog outputs 4/20mA (for dosing pumps) | |
1 digital alarm output | |
Working Chemicals |
Sodium Chloride /NaClO2 7.5% |
Hydrochloric Acid/HCl 9% | |
Drinking Water | |
Communications | VNC Server |